CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD

CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 1
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 2
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 3
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 4
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 5
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 6
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 7
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 8
  • CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD, фото 9
  • Под заказ
  • Код: TXN 120 05.11NSLN
clockОтправка с 04 июля 2026

от 63 520 ₴

+380 (68) 854-55-57
Павел
возврат товара в течение 14 дней по договоренности
CP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCDCP-2005 LTE - процессор, 2x Ethernet, 6 AI/DI, 6 RO, 2 AO, CIB, TCL2, LCD
от 63 520 ₴
Под заказ
+380 (68) 854-55-57
Павел
Описание
Характеристики
Информация для заказа
CP-2005 is a second-generation Foxtrot basic module, which is an optimal combination of a central unit with an integrated combination of 12 digital and analog inputs and outputs, compact size occupying a width of 6 modules on a DIN rail. It is thus possible to have a variant with a built-in LTE modem for direct connection to the Internet via a mobile operator. Of course, there are masters of both system expansion buses - TCL2 (up to 10 addressable modules) and two-wire CIB Common Installation Bus® (up to 32 addressable modules). It can therefore be extended in the same way as other basic modules. It is equipped with a total of 12 I / Os:     six multipurpose inputs, each of which can be used either as analog or as binary     two analog outputs for proportional control of various connected devices.     six separate relay outputs organized into two groups of three with their own common terminal Communication capabilities of the basic module CP-2005:     2x Ethernet interface 100 Mbit / s, each with up to 32 simultaneous connections (programming and general IP communication)     USB micro (programming)     USB A for Flas memory, WiFi adapter (client and AP - Access point) etc.     Variant with built-in LTE modem for direct wireless connection to the Internet via a mobile network operator     Slots for up to 4 optional serial interfaces RS-485, RS-232 24 V DC power supply, possibility of direct connection of a backup battery for uninterrupted operation in case of 230 V AC mains failures. CP-2005 is equipped with a new powerful central unit (CPU series L) with memory     1 MB for user program,     128 MB internal disk for storing files with parallel access from the LAN as a network disk,     16MB fast RAM disk     128/256 kB Datalobox     microSD card slot up to 1 TB     File management is provided by a journaling file system     Local communication with the user via OLED display (4 lines / graphic) and 6-key keyboard
DI3x DI/HSC
DI/AI6x DI/AI
DO6x RO
AI
AO2x AO
COM2x ETH 10/100
4x Serial channel (2x free slot)
1x USB device
1x USB host
1x TCL2 master
1x CIB master
SENSOR
System parameters of the central unit
Row of central unitI
User program memory1 MB
Memory for user variables / including RETAIN variables320 kB/48 kB
Instruction length4 Byte
Backup of program source code in PLCYes, optional in Mosaic
On-line program change in PLCYes, including I / O configuration change
DataBox - additional internal data memory128/257 kB, optional
File system - Internal Drive in PLC128 MB, journaling file system
File system - RAM disk PLC16 MB
File System - USB Flash DriveSupported
File system - Micro SD cardsupported (except for variants with WLAN1)
Optional memory card slotmicroSD - Card Slot (<= 1TB)
Cycle time per 1k of logic instructions0,036 ms
Cycle time for 1k integer operations0,044 ms
Cycle time for 1k floating point operations0,043 ms
Development environmentMosaic v2018.2 or higher
Programming languagesST, IL, LD, FBD, SFC, CFC
RTC - Real time circuitNo
RTC - Backup timetyp. 500 hours
Integrated Web serverYes
Integrated DataloggerYes
Access to PLC variables via web APIYes
COM - Communication - IP/Ethernet
Ethernet 10/100 Mb (ETHx)2
WLAN1 (internal, optional)1
WLAN2 (external via USB host, optional)1
LTE interface (LTEx, optional)1
Available system modes on ETH and WLANUNI, PC, PLC, PLD
Available system modes on LTEUNI - Exchange over UDP, TCP and support SSL / TLS encryption PC - EPSNET UDP / EPSNET TCP
TCP / IP protocolYes
UDP protocolYes
HTTPS protocolYes
HTTP protocolYes
WebSocket protocolYes
Protocol MODBUS/TCPYes
SMTP protocolYes
IEC 60870-5-104 protocolYes
REST APIYes
COM - USB
USB devices interface1x micro-USB
USB host interface1x USB-A
Available system modes on USBPC
COM - Serial channels
max. number of optional serial channels in the basic module4
number of slots for optional submodules with interface (MR-013x)2
max. number of expanding serial channels on the TCL2 bus6
Available system modes on CH5-10UNI, CSJ (CAN)
Modbus RTU / ASCII master protocolNo
Modbus protocol RTU/ASCII slaveNo
Profibus DP master protocol (<180 kbit/s)No
COM - System buses
TCL2 - system I/O bus1x TCL2 master
TCL2 - Range of one branch of the system I/O bus10 I / O modules + 4 operator panels + 6 serial channels
CIB - Common Installation Bus (R): Installation I/O bus1x CIB master (100 mA)
CIB - Address range of one branch of the installation bus32 CFox I/O modules
DI - Parameters of binary inputs DC (group A)
Number of inputs in group14
Common wireminus
Input typeType 1 (IEC)
Galvanic isolation of inputs from internal/peripheral circuitsNo
Diagnosticsindication of energized input by LED on module panel
Pulse input overload capacitymax. 30 V (t < 10 ms)
Input voltage for log. 00 V DC; -5 V DC min.; +5 V DC max.
Input voltage for log. 124 V DC; 15 V DC min.; 30 V DC max.
Input current at log. 1 (typ.)5 mA typ.
Delay from log. 0 to log. 1500 μs
Delay from log. 1 to log. 0500 μs
The minimum width of the captured pulse500 μs
NoticeNote that the GND terminals in the 24 V DC and ANALOG OUTPUTS arrays they are connected inside the system. It is not desirable to connect the GND terminal in the ANALOG field OUTPUTS with a negative pole power supply system also inputs as it would cross the other the GND terminal has closed the loop and thereby potentially induced interfering signals.
DI - Parameters of binary AC inputs
Total number of binary AC inputs1
Number of groups of AC inputs1
Number of AC inputs in group1
Organization of binary inputs into groups1x (DI14)
Input typeconventional switch
Galvanic isolation of internal circuitsYes
Input voltage for log. 00 V AC min., 120 V AC max.
Input voltage for log. 1230 V AC typ., 200 V AC min., 250 V AC max.
Input current at log. 1 (typ.)5 mA typ.
Delay from log. 0 to log. 110 ms
Delay from log. 1 to log. 010 ms
HSC - Special functions of binary inputs / counters
Unidirectional counter (UP)4x (DI4); (DI5); (DI8); (DI9)
PWM input (PWM)2x (DI4, DI5)
Overview of individual signal abbreviationsUP, UPB - pulse input for counter increment, counter B DOWN, DOWNB - pulse input for counter decrement, counter B CLK, CLKB - pulse input for counter, counters B DIR, DIRB - counter direction, counters B CLR - resetting the counter CAP - capture the counter value V - IRC's first track G - IRC second track NI - IRC zero pulse MD - measuring contact
HSC - Counter input parameters
Counter: Input frequency / resolution1 kHz
Pulse widthmin. 500 μs
Delay from log. 0 per log. 1500 μs
Delay from log. 1 per log. 0500 μs
Range of registersup to 32 bits, 0 to 4 294 967 296
DO - Parameters of binary transistor outputs (group A)
Number of transistor outputs2
Number of output groups1
Number of outputs in group2
Organization of transistor outputs into groups2 (DO11/AO0-DO12/AO1)
Common group conductorminus
Output typeMOSFET (Low-side switch)
Galvanic separation from internal circuitsNo
Switching voltage5 - 30 V DC
Switching current, output load0,5 A max.
Short-term output overload capacity3 A max.
Output resistancetyp. 0,16 Ω, max. 0,4 Ω
Switching timetyp. 9 μs
Opening timetyp. 13 μs
Internal protectionovervoltage, short circuit and overheating protection
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminalsDO0–DO5, DO7–DO10
Number of relay outputs11
Number of output groups3
Organization of relay outputs into groups3 (DO0-DO2) +3 (DO3-DO5) +5 (DO6-DO10)
DiagnoseAlarm signaling on panel module
Switching current3 A max., 100 mA min.
Switching voltage250 V AC max., 5 V AC min., 30V DC max.
Short-term output overload - inrush4 A max.
Current through common clamp10 A max.
Contact closing timetyp. 10 ms
Contact opening timetyp. 4 ms
Limit values of switched resistive loadmax. 3A at 30 V DC or 230 V AC
Switching inductive load limits DC13max. 3 A at 30 V DC
Switching inductive load limits AC15max. 3 A at 230 V AC
Switching frequency without loadmax. 300 switching / min.
Switching frequency with rated loadmax. 20 switching / min.
Mechanical lifemin. 5,000,000 cycles
Electrical life at maximum resistive loadmin. 100,000 cycles
Electrical life at maximum load inductive DC13min. 100,000 cycles
Electrical life at maximum load inductive AC15min. 100,000 cycles
Short-circuit protectionNo
Treatment of inductive loadExternal RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits3750 V AC
Isolation voltage between groups of outputs to each other3750 V AC
RO - Parameters of binary relay outputs (group B)
Parameters valid for the terminalsDO6
Switching current10 A max., 100 mA min.
Switching voltagemax. 250 V AC; max. 30 V DC; min. 5 V
Short-circuit protectionNo
Short-term output overload10A max.
Current through common clamp10 A max.
Contact closing timetyp. 10 ms
Contact opening timetyp. 4 ms
Limit values of switched resistive loadmax. 10A at 30 V DC or 230 V AC
Switching inductive load limits DC13max. 10 A at 30 V
Switching inductive load limits AC15max. 10 A at 230 V AC
Switching frequency without loadmax. 300 switching / min.
Switching frequency with rated loadmax. 6 switching / min
Mechanical lifemin. 5,000,000 cycles
Electrical life at maximum resistive loadmin. 100,000 cycles
Electrical life at maximum load inductive DC13min. 100,000 cycles
Electrical life at maximum load inductive AC15min. 100,000 cycles
Treatment of inductive loadExternal RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits3750 V AC
Isolation voltage between groups of outputs to each other3750 V AC
AI - Organization of analog inputs
Total number of analog inputs14
Number of inputs per group14
Number of analog input groups1
Organization of analog inputs into groups12 (DI0/AI0-DI5/AI5) (DI8/AI8-DI13/AI13) + 2 (DI6/AI6/AO2-DI7/AI7/AO7)
Input typeWith common clamp
Common wireMinus
Galvanic separation from internal circuitsNo
Diagnosticsoverload signaling in status word
External power supplyNo
Digital resolution12 bit
Converter typeApproximation
conversion time20 μs
Operating modesperiodic input sensing
Filtrationlow pass filter, digital comb filter 50/60 Hz
Insulation potential500 V DC between input and internal circuits
AI - Analog Input Ranges (Group A)
Voltage0 to 2 V / 805.9 μV
Input impedance in the voltage signal range> 20 kΩ
Voltage input error - max. error at 25 ° C± 0.4% of full scale
Voltage input error - temperature coefficient± 0.03% of full scale / K
Voltage input error - non-linearity± 0.07% of full scale
Voltage input error - repeatability under steady state conditions0.05% of full scale
Permissible continuous overload - voltage input-20 V to +30 V
Ccurrent0 to 20 mA / 8,059 μA
Current4-20 mA
Input impedance in the current signal range100 Ω
Current input error - maximum error at 25 ° C±0.4% of full scale
Error current input - temperature coefficient± 0.03% of full scale / K
Error current input - nonlinearity± 0.07% of full scale
Error current input - repeatability at steady-state conditions0.07% of full scale
Permissible continuous overload - current input, resistance 100 R± 5 V / 50 mA max
Open input detectionYes, in status word (under-range - only 4 - 20 mA range)
Passive sensorNTC Thermistor 20k / 25 °C (-40 to + 125 °C)
Input impedance in signal range RTD> 20 kΩ
Resistance measurement error - maximum error at 25 ° C± 0.5% of full scale
Resistance measurement error - temperature coefficient± 0.05% of full scale / K
Resistance measurement error - non-linearity± 0.09% of full scale
Resistance measurement error - repeatability at steady conditions0.07% of full scale
Detection of disconnected sensoryes, in status word, range overflow
AO - Analog output parameters
Number of outputs in group4
Organization of outputs in groups2 (DO11/AO0-DO12/AO1) + 2 (DI6/AI6/AO2-DI7/AI7/AO3)
Common wire of groupminus
Galvanic isolation from internal circuitsNo
Output typeactive voltage output
Converter resolution12 bit
conversion time10 μs
Analog output error - maximum error at 25 ° C± 2% of full scale
Analog output error - temperature coefficient± 0.3% of full scale / K
Analog output error - linearity± 0.7% of full scale
Analog output error - repeatability under steady state conditions± 0.5% of full scale
Voltage output - voltage0 - 10,5 V
Voltage output - Resolution 1 LSB2,589 mV
Voltage output - maximum output current10 mA
Power supply
Supply voltage, tolerances24 V DC, +25%, -15%, SELV
Maximum power input10 W
Module thermal/power loss12 W
Internal protectionYes, PTC reversible fuse
Power supply from ETH, passive PoE - input (appliance)ETH1/Power In
Power supply from ETH, passive PoE - output (source)ETH2 / Power out, jumper configuration
Power supply from ETH, passive PoE - injector parameters24 V DC, 1A
Size and weight
Weight approx.300 g
Product dimensions (width x height x depth)158 x 90 x 62 mm
Module width in multiples of M (17.5 mm)9M
Operating conditions, product standards
Product standardČSN EN 61131-2:2008 (idt IEC 61131-2:2007) - Programmable control units
Protection class of electrical objectII, according to ČSN EN 61140 ed.3: 2016 (idt IEC 61140:2016)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989)IP20
Operating areasNormal, acc. ČSN 33 2000-1 ed.2: 2009 (mod IEC 60354-1:2005)
Degree of pollution1, according to ČSN EN 60664-1 ed.2:2008 ( idt IEC 60664-1:2007)
Overvoltage category installationII, according to EN 60664-1 ed_2: 2008 (idt IEC 60641-1: 2007)
Type of deviceModule on DIN rail
Working positionVertical
Type of operation (operating frequency)Continuous
Ambient operating temperatures-20 °C to + 55 °C
Operating temperature maximum (° C)+55°C
Operating temperature minimum (° C)-20°C
Operating relative humidityfrom 10 % up to 95 % without condensation
Operating atmospheric pressuremin. 70 kPa (<3,000 m above sea level)
Storage temperatures–25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / EmissionB, according to EN 55032 ed. 2: 2017 (idt CISPR 32: 2015)
Emmisions - noteIn premises where the use of radio and television receivers can be expected to be used a distance of 10 m from these devices may cause radio interference. In such a case, the user may be required to take appropriate action.
Electromagnetic compatibility / Immunitymin. as required by EN 61131-2: 2007
Sinusoidal vibration endurance10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
DescriptionThe module is packed in a paper box according to the internal packing instructions. The package includes the following documentation. The outer packaging is carried out according to the scope of the order and the method of transport to the transport a package bearing the transport labels and other particulars necessary for transport. Transport from the manufacturer is carried out in the manner agreed upon when ordering. Product transport the customer's own means must be carried out by covered means of transport, in the specified position label on the packaging. The box must be stowed so as to prevent spontaneous movement a damage to the outer packaging. The product must not be exposed to direct weathering during transport and storage influences. Transport is allowed at temperatures from -25 ° C to +70 ° C, relative humidity 10% up to 95% (non-condensing) and a minimum atmospheric pressure of more than 70 kPa. Storage of the product is only allowed in clean rooms without conductive dust, aggressive gases and vapors. The most suitable storage temperature is 20 ° C
Installation
Assembly descriptionThe basic module is mounted vertically on the U-rail ČSN EN 50022. The installation of the assembly (basic module and peripheral modules, if applicable) is performed according to TXV 004 50.
Exchangeable submodulesThe optional MR-013x submodules of the serial interface are mounted in the base module CP-2007 on the bottom plate, which is accessible after removing the bottom of the housing. We only handle the module without power supply!
Connection
Connection of power and system communicationconnector with 2.5 mm2 screw terminal
Connection of inputs / outputsconnector with screw terminal 2.5 mm2
EthernetRJ-45
Serial channelsscrew-type connector 9x 1.5 mm2
USB device connectiontype micro B
USB host connectiontype A
Module operation
Module configurationThe module is operated, set and diagnosed from the MOSAIC programming environment. It is also possible to connect to the PLC using a web browser on port 8080. If the PLC has an IP address set eg 192.168.134.178 (default address on port ETH1, port ETH2 has DHCP enabled), just enter the address in the form http://192.168.134.178:8080 and the web browser displays the PLC configuration pages.
CommissioningThe module is ready for operation after connection of the supply voltage. The MODE button is available on the module panel to display the currently set IP address of the Ethernet interface. Parameters of all interfaces are set in the Mosaic programming environment. The exact setup procedure is given in the TXV 004 50 documentation.
Module diagnosticsThe basic diagnostic system of the module is part of its standard software. It operates from module power on and operates independently of the user. Diagnostic error states of the module and connected peripheral modules of the assembly are signaled on the module display and are available for processing by the master system. For more information, see TXV 004 50.
Maintenance
DescriptionThe module does not require any maintenance under general installation conditions.
NoticeBecause the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
GenerallyWarranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
NoticeYou must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.
Основные
ПроизводительTeco
Страна производительЧехия
СостояниеНовое
Пользовательские характеристики
DI3x DI/HSC
DI/AI6x DI/AI
DO6x RO
AO2x AO
COM2x ETH 10/100 4x Serial channel (2x free slot) 1x USB device 1x USB host 1x TCL2 master 1x CIB master
  • Цена: от 63 520 ₴