Корзина
Профиком
+380 (98) 363-64-36
Корзина

C-DM-0001B-SL Контроллер адресной RGB LED-ленты WS2812 (CIB)

C-DM-0001B-SL Контроллер адресной RGB LED-ленты WS2812 (CIB), фото 1
  • C-DM-0001B-SL Контроллер адресной RGB LED-ленты WS2812 (CIB), фото 2
  • Под заказ
  • Код: TXN 133 81
clockОтправка с 10 октября 2026

от 5 531 ₴

+380 (98) 363-64-36
возврат товара в течение 14 дней по договоренности
C-DM-0001B-SL Контроллер адресной RGB LED-ленты WS2812 (CIB)C-DM-0001B-SL Контроллер адресной RGB LED-ленты WS2812 (CIB)
от 5 531 ₴
Под заказ
+380 (98) 363-64-36
Описание
Характеристики
Информация для заказа
C-DM-0001B-SL is a module connectable to the CIB bus of the Foxtrot system. It contains one DO output for data addressable RGB LED chips type WS2812B, one IN / OUT terminal for synchronization of several modules in a row and a voltage source of 5 V / 1 A for powering a series of up to 16 LEDs. It is equipped with a slot for a microSD card, on which data files for static and dynamic effects are uploaded. which the module "reads" and cyclically sends to a series of connected LED chips.
DI
DI/AI
DO1x DO (data)
1x SYN (in/out)
AI
AO
COM1x CIB slave
SENSOR
COM - System buses
CIB - Common Installation Bus (R): Installation I/O bus1x CIB slave
DI - Parameters of binary inputs DC (group A)
Parameters valid for inputs on the terminalsDI/AI1, DI/AI2
Number of inputs in group2
Common wireminus
Combined input typeDI/AI Active, for sensing potential-free contacts and measuring resistance sensors
Galvanic isolation of inputs from internal/peripheral circuitsNo
Balanced resistance input2× 1k1 (tamper/0/1/tamper)
RO - Parameters of binary relay outputs (group A)
Parameters valid for the terminalsDO1
Number of relay outputs1
Output typeelectromechanical relay, unprotected output
Contact typeNO - Normally Open
Switching current3 A max., 100 mA min.
Switching voltage250 V AC max., 5 V AC min., 30V DC max.
Mechanical lifemin. 5,000,000 cycles
Electrical life at maximum resistive loadmin. 200,000 cycles
Short-circuit protectionNo
Treatment of inductive loadExternal RC element, varistor (AC), diode (DC)
Insulation voltage between outputs and internal circuits3750 V AC
AI - Organization of analog inputs
Total number of analog inputs2
Number of inputs per group2
Number of analog input groups1
Input typeWith common clamp
Common wireGND terminal
Galvanic separation from internal circuitsNo
Diagnosticsoverload signaling in status word
Digital resolution10 bit
AI - Analog Input Ranges (Group A)
Parameters valid for inputs on the terminalsDI/AI1, DI/AI2
Passive sensorNTC Thermistor 12k / 25 °C (-40 to + 125 °C)
DI: Voltage-free contact0 when> 1.5 kOhm, 1 when <0.5 kOhm
DI: Balanced resistance input2x 1k1 (tamper/0/1/tamper)
Resistance measurement error - maximum error at 25 ° C± 0.5% of full scale
AO - Analog output parameters
Galvanic isolation from internal circuitsNo
Output typeactive voltage output
Voltage output - voltage0 - 10 V
Voltage output - Minimum resolution1 %
Voltage output - Adjustable range0 ÷ 130 % Ujm
Voltage output - Load resistance>1 kΩ
Voltage output - Load capacity250 nF
Power supply
Supply voltage, tolerances24/27 V DC from CIB bus
Power supply from CIB - typical current consumption (mA)18 mA
Power supply from CIB - maximum current consumption (mA)25 mA
Power supply from CIB - Galvanic separation of power supply from internal circuitsRelay output contact only
Insulation voltage of galvanic separation4 000 VAC (50/60 Hz) 1 min.
Insulation resistance1 MΩ min. (at 500V)
Power supply from CIB - internal protectionYes, returnable fuse
Size and weight
Weight approx.7 g
Module width55 mm
Module height26 mm
Module depth20 mm
Product dimensions (width x height x depth)55 x 26 x 20 mm
Operating conditions, product standards
Product standardČSN EN 60730-1 ed. 2:2001 (mod IEC 60730-1:1999)
Protection class of electrical objectIII, according to ČSN EN 61140: 2003 (idt IEC 61140: 2001)
IP rating (Ingress Protection) according to ČSN EN 60529: 1993 (idt IEC 529: 1989)IP10B
Operating areasNormal according to ČSN 33 2000-1: 2003 (IEC 364-1: 1992 mod)
Degree of pollution1, according to ČSN EN 60664-1: 2004 (mod IEC 60664-1: 1992)
Overvoltage category installationII, acc. ČSN EN 60664-1:2004 (mod IEC 606641:1992)
Type of deviceIn the installation box, under the cover
Working positionAny
Type of operation (operating frequency)Continuous
Ambient operating temperatures0 °C to + 55 °C
Operating temperature minimum (° C)0°C
Operating relative humidityfrom 10 % up to 95 % without condensation
Operating atmospheric pressuremin. 70 kPa (<3,000 m above sea level)
Storage temperatures–25 °C to +70 °C
Electromagnetic compatibility, Mechanical endurance
Electromagnetic compatibility / EmissionB, according to EN 55022: 1999 (mod CISPR22: 1997)
Electromagnetic compatibility / Immunitymin. according to ČSN EN 60730-1 ed.2: 2001
Sinusoidal vibration endurance10 Hz to 57 Hz, amplitude 0,075 mm, 57 Hz to 150 Hz, acceleration 1 G (Fc test according to EN 60068-2-6: 1997 (idt IEC 68-2-6: 1995), 10 cycles per axis.)
Packaginng, transportation, storage
DescriptionМодуль упакован в антистатический пакет. Эта документация также является частью пакета. Внешняя упаковка осуществляется в соответствии с объемом заказа и способом транспортировки в транспортной упаковке, снабженной этикетками и другими данными, необходимыми для транспортировки. Продукт не должен подвергаться воздействию прямых погодных условий во время транспортировки и хранения. Соложение продукта разрешено только в чистых помещениях. без токопроводящей пыли, агрессивных газов и паров. Наиболее подходящая температура хранения - 20 ° C.
Installation
Assembly descriptionThe module is inserted freely into the installation box or attached with a suitable cable tie inside the device. The conductors of the supply ribbon cable can be separated and shortened as required. However, to prevent interference problems, the active conductors must be routed together with the common GND conductor to the sensor so that no interference loops form between the conductors. Best with twisted pair cables.
Connection
Connection of power and system communicationRibbon flat conductors 0.15 / 0.5 mm2
Module connectionStrip wires 0.15 mm2, relay 2x 0.5 mm2
Module operation
CommissioningThe module is operated, set and diagnosed from the MOSAIC programming environment or other parameterization software. The module is ready for operation after connecting the supply voltage and the CIB bus. The HW address is indicated on the label on the module.
Module diagnosticsThe basic diagnostics is performed internally and the result is available in the relevant registers of the Mosaic environment.
Maintenance
DescriptionThe module does not require any maintenance under general installation conditions.
NoticeBecause the module contains semiconductor components, it is necessary to follow the principles for working with electrostatic sensitive components when handling the removed cover. It is not allowed to directly touch the printed circuit boards without protective measures !!!
Warranty
GenerallyWarranty and complaint conditions are governed by the Terms and Conditions of Teco a.s.
NoticeYou must meet all the conditions of this documentation before turning on the system. The system must not be put into service unless it has been verified and confirmed that the machinery meets the requirements of Directive 89/392 / EEC, in so far as it applies to it. Documentation subject to change.
Основные атрибуты
ПроизводительTeco
Страна производительЧехия
СостояниеНовое
Пользовательские характеристики
DO1x DO (data) 1x SYN (in/out)
COM1x CIB slave
  • Цена: от 5 531 ₴